The diesel generator ON and OFF

Update:2017-06-04 15:39Author:admin
First, the manual start 1, the generator manually start: first test the alarm system as normal, the control switch change to the manual (MAN) position, the generator can start by itself. 2, the generator OFF.The control switch change to th
First, the manual start
 
1, the generator manually start: first test the alarm system as normal, the control switch change to the manual (MAN) position, the generator can start by itself.
 
2, the generator OFF.The control switch change to the stop (STOP) position or press the red emergency stop button to stop the generator running. In emergency case, you can press the emergency stop button to force to the shutdown.After press the red emergency stop button must return to the original position, otherwise the generator will not start again.
 
Second, automatic switching control
 
1,Put the control switch to the automatic (AUTO), and with the power switch (ATS) control switch must also be placed in automatic position, when the electricity is stopped, ATS will transfer signal to the generator control System, the generator will automatically start.
 
2, when the control switch change to stop position (STOP), or remain in the automatic, but the electricity has been restored,the ATS sent a stop signal, the generator will automatically stop.
 
Note: In the event of an automatic shutdown due to the fault (over speed, high water temperature, low oil pressure, etc.), the fault reset button must be ready to restart after troubleshooting.
Diesel generator operation note:
 
1. AC ammeter: the needle indicates whether the normal, change the current switch, measure the phase between the phase current value, the phase difference is better not more than 10%.
 
2. AC voltmeter: the needle indicates whether the voltage is normal.
 
3. The oil pressure indicates whether the oil pressure is in the normal range.
 
4. Charging meter: whether the pointer in the (+) direction.
 
5. The water temperature meter indicated by the water temperature table is in the normal range of 65 ° C to 93 ° C.
 
6. Speed meter: the speed of the engine is appropriate. (1800 rpm at 60 Hz)
 
7. The generator engine if have abnormal sound or vibration
--------------------------------------------------------------------------------------
TEL: +86 536 8185702
Mob£º+86 15905360231
SKYPE: huaquanpower
Wechat/whatApp:+86 15905360231
EMAIL: hqpower@huaquanpower.com
ADD: Xinzheng Industrial Park£¬Qingyuan West Street£¬Weifang Economic Development Zone,Shandong Province,China
--------------------------------------------------------------------------------------

Source:http://www.china-quan.com/en/News/Company_News/544.html

Copyright Shandong HQ power co., LTD All rights reserved.